BT SRC32 Install for Window 2000 or Windows XP
| The Broadcast Tools SRC32 unit allows one to use an expandable GPI/O interface with DAD. | ||
| NOTE: Support for these units was added in DAD 4.2k28 (Jun.06.03) | ||
Configuration of DAD:
Start up DAD. After DAD has loaded, go to SETUP and select CFI & README. Open the workstation’s CFI file.
Find the [SERIAL] section and edit the COMx_INFO line:
COM2_INFO=38400 N 8 1
In the [EXTERNAL_DEVICES] section:
REMOTE=BTSRC32 2
REMOTE_PROCESS_DELAY=0
GPO_GPI=32 32 64
GPI_REVERSE_SENSE=ON
|
|
NOTE: This guide is using Com Port 2. If you are using a different Com Port, please adjust the COMx_INFO line and the REMOTE line accordingly. For example: Comx_INFO is: Com<port number>_INFO=38400 N 8 1 REMOTE is: REMOTE=BTSRC32 <port number> |
Save the changes and close the file. Hit the yellow REFRESH Button, then EXIT DAD. Once DAD has exited, reboot the PC.
Configuration of the BTSRC32 unit:
Inside the SRC32 unit one must set the Dip Switch accordingly. [0=off / 1=on]
|
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
|
ON |
|
|
x |
x |
x |
|
|
x |
|
OFF |
x |
x |
|
|
|
x |
x |
|
Notes on Dip Switch options
|
Switch |
1 & 2 |
3 & 4 |
5 |
6 |
7 |
8 |
|
Setting |
0 0 = unit 0 (master) 0 1 = unit 1 1 0 = unit 2 1 1 = unit 3 |
0 0 = 9600 0 1 = 2400 1 0 = 19200 1 1 = 38400
|
On = Hex Off = ASCII
|
On = Pair Off= normal
|
Modem mode not supported |
invert LCD display status On = [closed=1 / open=0] Off = [closed=0 / open=1]
|
One must also change the internal jumper number 13 from EXTERNAL to RS232.
Failure to do so could result in the ability to use GPI's but NOT the ability to use GPO's.
|
|
Other Notes: When using more than one unit, one must set the dip switches on each unit accordingly. DAD MUST talk to the unit that is defined as the Master (unit 0). The sync cable between the units must be connected to the EXT2 on the master and connected to the EXT1 on the slave unit.
Also, one must remember to modify the DAD workstation CFI file to reflect the proper amount of inputs and outputs. For example: GPO_GPI=64 64 128 |
|
|
IMPORTANT: If one has followed all instructions above and can not get the unit to function properly, there is a chance that one MIGHT have to install the DADPIO with the default address.
For example, run the C:\DAD\DRIVERS\INSTALL.BAT file
This will install the DADPIO with the default address of 300. |